Features: Crossflow fiberglass Cooling
Towers contain BHZ series and HBL series.
BHZ series contain low noise type and
super low noise type, the single tower
cooled water volume is 80;100;125;150;175;200m3/h. with its features of low air flow speed and low noise make it suit to the places where have
strict demand of noise level. The cooled
water volume could reach 1200m3/h when installed. Besides the above two types, HBL series also
contain industry type for cooling of
middle and high temperature water. the single tower cooled water volume is 300;500;700m3/h, they are also can be used concatenated. It havefeatures ashigh speed flow ,compared higher
noise than composed tower(lower than
return flow tower) and less ground
occupied. Codes of
two series:
B——Fiberglass H——Cross flow tower
z——Composed style L——Cooling tower Installation size of HBLCD
power saving low noise fiberglass cross
flow cooling tower
Type
L
L1
H
h1
h2
h3
h4
h5
h6
h7
h8
L1
L2
L3
AHBLCD-300
10650
7250
6230
700
3330
2200
270
400
150
250
350
1680
1895
275
AHBLCB-500
11640
8030
7030
700
4137
2193
270
460
150
250
350
1680
2285
260
AHBLCD-700
12540
8930
7080
750
4137
2193
270
450
200
400
400
1680
2735
260
塔型
L4
L5
L6
B
B1
B2
B3
h9
Dg1
Dg1
Dg2
Dg3
Dg4
Dg5
Dg6
AHBLCD-300
775
1500
1700
3810
1033
1434
155
1300
200×2
125×2
300
40
40
80
50
AHBLCB-500
775
1500
1805
4650
1483
1374
155
1300
200×2
125×2
300
50
50
100
50
AHBLCD-700
775
1500
1805
6640
1425
3400
155
2200
200×4
150×4
350
65
65
100
50
Installation size of HBLCD
power saving low noise 、HBLG industry type fiberglass cross flow cooling tower
Type
B
H
L
l1
L2
L3
L4
L5
B1
B2
B3
h1
h2
HBLD-300
3810
4514
7250
1710
1700
860
1500
6940
1218
1264
55
700
3333
HBLG-300
3810
4514
7250
1710
1700
860
1800
6940
1218
1264
55
700
3333
HBLD-500
4650
5320
8030
1710
2040
850
1500
7620
1498
1544
55
700
3470
HBLG-500
4650
5320
8030
1710
2040
850
1800
7620
1498
1544
55
700
3470
HBLD-700
6640
5370
8930
1710
2485
855
1500
8500
1615
3310
50
750
4137
HBLG-700
6640
5370
8930
1710
2485
855
1800
8500
1615
3310
50
750
4137
Type
h1
h4
h
Dg1
Dg2
Dg3
Dg4
Dg5
Dg6
HBLD-300
483
270
1200
200×2
300
40
40
80
50
HBLG-300
483
270
1200
200×2
300
40
40
80
50
HBLD-500
483
270
1200
200×2
300
50
50
100
50
HBLG-500
483
270
1200
200×2
300
50
50
100
50
HBLD-700
483
270
2000
200×4
350
80
80
100
50
HBLG-700
483
270
2000
200×4
350
80
80
100
50
Installation size and shape
of HBLCD power saving low noise fiberglass
cross flow cooling tower
Type
L
H
B
l1
L2
L3
L4
L5
B1
B2
B3
h1
h1
HBLCD-300
10650
3810
6230
1710
1700
2550
1500
1830
1218
1264
55
700
3333
HBLCD-500
11640
4650
7030
1710
2040
2655
1500
1985
1498
1544
55
700
3470
HBLCD-700
12540
6640
7080
1710
2485
2655
1500
1985
1615
3310
50
750
4137
Type
h1
h4
h
Dg1
Dg2
Dg3
Dg4
Dg5
Dg6
HBLCD-300
2197
270
1200
200×2
300
40
40
80
50
HBLCD-500
2860
270
1200
200×2
300
50
50
100
50
HBLCD-700
2193
270
1200
200×2
350
80
80
100
50
Installation size
of 1000-3000T/H high temperature cross
flow cooling tower for industry
Type
HBLG-1000
HBLG-1500
HBLG-2000
HBLG-2500
HBLG-3000
L
12800
13900
16700
17300
18400
l1
2750
2750
3350
3350
3350
l2
3650
4200
5000
5300
5850
l3
1285
1285
1285
1285
1285
b
3600
5100
5700
7200
7200
b1
1800
2550
2850
3600
3600
B
7200
10200
11400
14400
14400
H
6620
6620
7620
7620
8620
h
6000
6000
7000
7000
8000
Dg1
200
250
300
300
350
Dg2
300
350
400
450
500
ØF
6000
7000
8500
9000
10000
Flow volume(G)
748km3/h
1112m3/h
1516m3/h
1819m3/h
2224m3/h
Power(N)
45Kw
75KW
90KW
110KW
132KW
State
weight(t)
27.5
38
48.5
59.0
68
湿重T
41.5
57
70.5
84.0
98.0
Noise dB(A)
67
68.0
72
73
75
Instruction :
1.Design according the follow
working condition: temperature of flow-in
water t1=43℃, temperature of
flow-out water t2=33℃, temperature of watery ball t=28℃,atmosphere
Pa=753mmHg,, water cooling temperature
t=10℃, close temperature
t2-t=5℃.
2.The water is introduced by
pipelines from both sides. If water will
be introduced from one side, the main
pipeline will be thicker and set out the
side of air stack, the other side pipeline
should cross the air stack of tower top.
3.表中标准点噪声值,侧点为进风窗前塔体平面的当量直径远,距地面1.5米高.
Type
l1
l2
b
L
B
N
W
HBLG-1000
2750
3650
3600
12800
7200
3
21.6N
HBLG-1500
2750
4200
5100
13900
10200
3
30.6N
HBLG-2000
3350
5000
5700
16700
11400
3
34.2N
HBLG-2500
3350
5300
7200
17300
14400
3
43.2N
HBLG-3000
3350
5850
7200
18400
14400
3
43.2N
Affix :
1.N is the number of
concatenated machines, N=3.
2.The depth H, the size and
position of flow-out water pipe, polluted
water pipeline and absolutely drainage are
determined by the real condition. (suggest
H=1500mm ).
3.The steel concrete water
pool is designed and found by units, for
instance adopting blueprint designed by
the fourth design institute of Luoyang
agricultural mechanic committee. Customers
could send mails or directly come here to
supply the project geological documents,
and design by the forth institute or
design by the customer-self. The basic
load and still anchor are supplied by the
fourth institute.
Main
parameter ofHBLCD power saving low noise fiberglass cross flow cooling tower
Type parameter
Cooling water volume when T=28℃
m3/h
Cooling water volume when T=27℃
Dimesion
Flow volumem3/h
Diameter of fan blade(mm)
Motor voltage(KW)
Weight(T)
Noise level dB(A)
Δt=5℃
Δt=8℃
Δt=5℃
Δt=8℃
Length
Width
Height
State
weight
Weight
during running
HBLD-300
300
225
343
255
7250
3180
4410
167000
3400
7.5
5.85
13.38
59.0
HBLD-500
500
377
576
427
8040
4650
5230
260000
4200
11.0
9.20
17.24
61.6
HBLD-700
700
528
803
596
8940
6640
5319
370000
5000
18.5
12.95
26.05
62.6
HBLCD-300
300
225
343
255
10650
3810
6210
167000
3400
7.5
7.05
14.18
52.5
HBLCD-500
500
377
576
427
11640
4650
7030
260000
4200
11.0
10.80
18.84
53.7
HBLCD-700
700
528
803
596
12540
6640
7119
370000
5000
18.5
14.75
25.81
54.5
Main parameter of
HBLCD power saving low noise 、HBLG industry type fiberglass cross flow cooling(noise is generated by the
dynamic retarder)
Type parameter
Cooling water volume when T=28℃ m3/h
Cooling water volume when T=27℃
Dimesion
Flow
volume m3/h
Diameter of fan blade(mm)
Motor voltage(KW)
Weight(T)
Noise level dB(A)
Δt=10℃
Δt=15℃
Δt=25℃
Length
Wdth
Height
State
weight
Weight
during running
HBLG-300
300
288
265
7250
3810
4410
200000
3400
11.0
6.13
13.66
64.5
HBLG-500
500
487
450
8040
4650
5230
320000
4200
18.5
9.42
17.46
65
HBLG-700
700
669
530
8940
6640
5319
450000
5000
30
13.19
26.29
66
Instruction :
1.Taking the temperature of
watery t=28℃, flow in water temperature
of low noise and super low noise t=37℃, flow-out water temperature t=32℃, that isΔt=5℃, t2-t=4℃ . For industry type,
temperature of high temperature tower t=28℃,t=43℃,t=33℃, that isΔt=10℃t2-t=5℃.
2.Temperature of the cooling
water t=28℃ and t=27℃,t1=37℃,t2=32℃ort1=40℃,t2=32℃of low noise type.
There are also cooling water temperatures
t1=60℃,t2=35℃及t1=55℃,t2=35℃ of industry type.
3.the noise is measured air
inlet window or the screen diameter far,
1.5m above ground, diameter D=1.13√L×B.
Parameter of DBHZ
series power saving low noise fiberglass
cross flow composed cooling tower